Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 1615 Volume (gallons): 63447 Flow measure reading (gpm): 80 Minimum required flow (gpm): 132
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min): 480
Total Chlorine (ppm): 3 Free Chlorine (ppm): 3 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 80 Pool water temp ˚F: 74 pH: 7.5 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 98 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat The licensee was unable to provide equipment replacement notification form that approved the new filters.
Provide form to prove the new filters are approved for use.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat SVRS test results/service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
The left flow meter was not functioning correctly.
Repair the flow meter to ensure flow and turnover rate can be calculated.
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 18-June-2015

Comments
-The disinfectant residuals and water quality parameters met code requirement.
-All required safety equipment was provided.
-The pool perimeter was secure.
-The filter pressure was 14 psi.
-The pool water was clear.
-Turn over rate was approximately 6.6 hours. There were two flow meters. The left flow meter was not functioning and the right flow meter was measured at 80 gpm.
If you have any questions or concerns, call me at (513) 732-7612.