Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1800 | Volume (gallons): 54000 | Flow measure reading (gpm): | Minimum required flow (gpm): 113 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 606 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 6 | Free Chlorine (ppm): 6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 110 | Pool water temp ˚F: 83 | pH: 8.0 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP noted at 606.
Have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Unable to read flow meter/flow meter was stuck. Ensure new flow meter is installed.
All equipment must be maintained in accordance with the manufacturers specifications. 3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH noted at 8.0
Treat the pool water so that the pH is within the acceptable range.
Comments |
---|
Inspection Notes: 1. Water was clear at time of inspection. 2. pH noted at 8.0. Ensure pool is properly treated so that pH is between 7.2-7.8 3. Ensure alkalinity is tested weekly. 4. Unable to read flow meter accurately. 5. Chlorine was above 1ppm. Thank you! |