Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 136 | Volume (gallons): 1530 | Flow measure reading (gpm): 55 | Minimum required flow (gpm): 13 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 555 | Turnover Rate (min): 120 |
Total Chlorine (ppm): 2.5 | Free Chlorine (ppm): 2.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 90 | Pool water temp ˚F: 80 | pH: 7.5 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 38 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv.
Recalibrate ORP probe. If necessary, have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. Pressure switch / pump interlock bypassed (unplugged).
Activate pressure switch as required. Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. 3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
No pool records for this pool week found in the folder. The licensee /authorized representative was not keeping or maintaining operational records.
Record pool water tests in accordance with code requirements. All facility records must be maintained and available for review upon request. 3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. No records for this week found in folder.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use. 3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use. 3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features.
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use pH must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the pH must be tested at 1 special feature every 6 hours the sprayground or spray feature is in use. 3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Corrected During Inspection Equipment was not maintained per manufacturers specifications. Observed flow rate of 55 gpm exceeds the maximum filter capacity for the sand filter.
Throttle flow rate so that it does not exceed filter capacity ( between 13-38 gpm). All equipment must be maintained in accordance with the manufacturers specifications. Service tech for Aquamarine Pool Service throttled flow to 30-35 gpm during inspection. Thank you. 3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
Comments |
---|
Pool water clarity, disinfectant residual and water quality readings meet code requirements at this time. The pool looks great! Please maintain records as required. |