Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 150 | Volume (gallons): 1000 | Flow measure reading (gpm): | Minimum required flow (gpm): 8 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 240 | Turnover Rate (min): |
Total Chlorine (ppm): 0 | Free Chlorine (ppm): 0 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 50 | Pool water temp ˚F: 74 | pH: 7.5 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv. ORP noted at 240.
Have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection Chlorine disinfectant residual was less than 1 ppm for the pool. Operator adjusted chlorine and levels were noted at 1ppm.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. 3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Flow meter was stuck below 40. Unable to read.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. 3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm. Chlorine was adjusted and noted at 1ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Comments |
---|
Pool Notes: -Safety equipment available. -Phone properly working. -Ensure that chlorine is at least 1ppm, 2-4ppm is the recommendation for pools. -Ensure to increase alkalinity to at least 60. -Wading pool was not being fed do to machine stating feed limit reached. Operator came and adjusted system so that chlorine was being fed to pool. -Pool noted at 1ppm chlorine. -Flow meter was stuck at bottom and unable to determine turnover rate. |