Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1840 | Volume (gallons): 62400 | Flow measure reading (gpm): | Minimum required flow (gpm): |
Disinfectant: | Secondary Disinfectant: | ORP: 676 | Turnover Rate (min): |
Total Chlorine (ppm): 3 | Free Chlorine (ppm): 3 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 120 | Pool water temp ˚F: 79 | pH: 7.9 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Flow meter does not allow for proper reading of flow rate. The flow rate appeared higher than the flow meter was able to read.
All equipment must be maintained in accordance with the manufacturers specifications. 3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/chemical/storage was propped open. Accesible to public.
Pool equipment and chemical storage should only be accesible to authorized personnel. 3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. Observed to be 7.9
Treat the pool water so that the pH is within the acceptable range.
Comments |
---|
Phone operable, first aid kid provided. The flow rate was unable to be determined. The flow rate appeared higher than could be read on flow meter. The flow meter should allow proper reading to be observed. The pump room was propped open. The pump room and chemical storage should only be accessible by authorized personnel. Chlorine and alkalinity was at required levels, but pH was found to high. |