Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1840 Volume (gallons): 62400 Flow measure reading (gpm): 95 Minimum required flow (gpm): 130
Disinfectant: Secondary Disinfectant: ORP: 709 Turnover Rate (min): 480
Total Chlorine (ppm): 3 Free Chlorine (ppm): 3 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 50 Pool water temp ˚F: 80 pH: 6.8 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 141 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Skimmer weirs were missing.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Corrected During Inspection pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. pH was raised to 7.2.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Corrected During Inspection Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 10-August-2016

Comments
Inspection notes:
- Pool water was clear.
- Safety equipment was provided.