Sampling Details
Sub Type: Apartment/Condo Special Feature: Location:
Area: 900 Volume (gallons): 25178 Flow measure reading (gpm): 55 Minimum required flow (gpm): 52
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 665 Turnover Rate (min): 457
Total Chlorine (ppm): 5 Free Chlorine (ppm): 5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 80 Pool water temp ˚F: 85 pH: 7.7 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 20-June-2024

Comments
Proper safety equipment available.
Water chemistry within required parameters.
Ensure that VGB cover information is up to date.