Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 900 | Volume (gallons): 25178 | Flow measure reading (gpm): 60 | Minimum required flow (gpm): 53 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 785 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 1.5 | Free Chlorine (ppm): 1.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 83 | pH: 7.9 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 98 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Weirs are missing from the skimmer baskets. Replace the missing weirs.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. 3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat The pool pH was noted at 7.9 (Between 7.8-8.0). Lower, then maintain the pool pH between 7.2-7.8.
Treat the pool water so that the pH is within the acceptable range.
Comments |
---|
Pool Notes: 1. The pool water is clear. 2. ACC unit pH noted at 7.6. 3. Pool turnover rate=7.0 hours. 4. ACC unit Alarm functioned when tested. 5. The report was emailed to Ms. Lasota. Contact Scott Bradley,R.E.H.S. (732-7614) with any questions. |