Sampling Details
Sub Type: Other Special Feature: Location:
Area: 1696 Volume (gallons): 52000 Flow measure reading (gpm): 100 Minimum required flow (gpm): 109
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: Turnover Rate (min):
Total Chlorine (ppm): 3 Free Chlorine (ppm): 3 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 90 Pool water temp ˚F: 85 pH: 7.4 Cyanuric acid (ppm):
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 74 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
No records of the periodic testing of the ACC unit could be located.
Test and record the results of the periodic testing of th ACC unit.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 04-August-2015

Comments
No other violations observed during the inspection.
The pool otherwise looks great!
Pool Notes:
1. The 2015 pool license is posted.
2. The pool water is clear.
3. Proper safety equipment is available for use.
4. ACC unit pH noted at 7.5.
5. Pool turnover rate=8.7 hours. A flow rate of 108-110gpm would need to be maintained to insure an eight (8) hour turnover rate.
6. Copy of the report was left with the pool records.
Inspection conducted by Scott Bradley,R.S. 732-7614