Sampling Details | |||
---|---|---|---|
Sub Type: Apartment/Condo | Special Feature: | Location: | |
Area: 1615 | Volume (gallons): 63447 | Flow measure reading (gpm): 140 | Minimum required flow (gpm): 132 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: | Turnover Rate (min): 480 |
Total Chlorine (ppm): 0.6 | Free Chlorine (ppm): 0.6 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 100 | Pool water temp ˚F: 78 | pH: 7.3 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 98 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested every four hours.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when the pool is open for use. 3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Repeat Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. 3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
pH was not tested every four hours.
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. 3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat All skimmer weirs were missing.
Replace all missing skimmer weirs. 3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Corrected During Inspection Pool free chlorine disinfectant residual was measured at 0.6 ppm.
Pool free chlorine was increased to 1 ppm.
Comments |
---|
-The disinfectant residuals and water quality parameters meet code requirement. -All required safety equipment was provided. -The pool perimeter was secure. -The filter pressure was 12 psi. -The pool water is clear. -The Stingl switch was functioning correctly. -Turn over rate was 453 minutes. If you have any questions or concerns, call me at (513) 732-7612. |