Sampling Details | |||
---|---|---|---|
Sub Type: Wading Pool | Special Feature: | Location: | |
Area: 136 | Volume (gallons): 1530 | Flow measure reading (gpm): 25 | Minimum required flow (gpm): 13 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 640 | Turnover Rate (min): 120 |
Total Chlorine (ppm): 5 | Free Chlorine (ppm): 5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 70 | Pool water temp ˚F: 74 | pH: 7.7 | Cyanuric acid (ppm): 0 |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): 38 | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mV.
Clean and recalibrate ORP probe. If this does not solve the problem, have the ACC unit inspected to determined why the ORP is low.
Comments |
---|
Water clarity disinfectant residuals and water quality readings meet minimum code requirements. Thank you. |