Sampling Details
Sub Type: Wading Pool Special Feature: Location:
Area: 136 Volume (gallons): 1530 Flow measure reading (gpm): 25 Minimum required flow (gpm): 13
Disinfectant: Sodium Hypochlorite Secondary Disinfectant: ORP: 640 Turnover Rate (min): 120
Total Chlorine (ppm): 5 Free Chlorine (ppm): 5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 70 Pool water temp ˚F: 74 pH: 7.7 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): 38 Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mV.
Clean and recalibrate ORP probe. If this does not solve the problem, have the ACC unit inspected to determined why the ORP is low.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 28-August-2017

Comments
Water clarity disinfectant residuals and water quality readings meet minimum code requirements. Thank you.