Sampling Details
Sub Type: Wading Pool Special Feature: Location:
Area: 150 Volume (gallons): 1000 Flow measure reading (gpm): 50 Minimum required flow (gpm): 8
Disinfectant: Secondary Disinfectant: ORP: 601 Turnover Rate (min):
Total Chlorine (ppm): 1.5 Free Chlorine (ppm): 1.5 Combined Chlorine (ppm): 0 Total Bromine (ppm):
Alkalinity (ppm): 80 Pool water temp ˚F: 85 pH: 7.6 Cyanuric acid (ppm): 0
Spa water temp ˚F: Spa water replaced every 30 days: Max Allow. Filter Flow (gpm): Max Allow. Flow: Jet pump capacity (gpm):
Max Allow. Flow: SF pump capacity (gpm):
[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation. Pressure gauge on filter not functioning.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.


Inspection Information


[?] Facility Type: Pool

[?] Inspection Type: Standard

[?] Inspection Date: 27-June-2019

Comments
Pool water is clear.
Safety equipment available.
Required signs are posted.
Julie Michelson present during inspection.
Julie recalibrated the ACC during inspection.
Pool looks good, keep up the good work.