Sampling Details | |||
---|---|---|---|
Sub Type: Other | Special Feature: | Location: | |
Area: 1650 | Volume (gallons): 51000 | Flow measure reading (gpm): 80 | Minimum required flow (gpm): 106 |
Disinfectant: Sodium Hypochlorite | Secondary Disinfectant: | ORP: 635 | Turnover Rate (min): 480 |
Total Chlorine (ppm): 2.5 | Free Chlorine (ppm): 2.5 | Combined Chlorine (ppm): 0 | Total Bromine (ppm): |
Alkalinity (ppm): 120 | Pool water temp ˚F: 77 | pH: 7.6 | Cyanuric acid (ppm): |
Spa water temp ˚F: | Spa water replaced every 30 days: | Max Allow. Filter Flow (gpm): | Max Allow. Flow: Jet pump capacity (gpm): |
Max Allow. Flow: SF pump capacity (gpm): |
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat The ACC unit ORP 635mv. Increase the reading to 650mv minimum.
Have the ACC unit inspected to determined why the ORP is low. 3701-31-04 (A)(1) / Public swimming pool shall be licensed
The Swimming Pool license could not be located. Locate, then post the current Swimming Pool license.
3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
The is no soap in the men's rest room. Provide soap in the rest room.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat The flow meter was noted at 80gpm. For an 8 hour turnover, increase the flow rate to 106gpm minimum.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required. The pool free chlorine residual was noted at 0ppm. Increase, then maintain the residual at 1.0ppm minimum. Ms. Michelson agreed to Voluntarily Close the pool. A POOL CLOSED sign was posted. Correct By: 06-Jun-2023 |
3701-31-04 (B)(6)(s)/Perimeter barrier is in good repair to prevent unauthorized entry The pool entrance gate was not self closing, and would not latch. Repair the gate. Ms. Michelson agreed to Voluntarily Close the pool. A POOL CLOSED sign was posted. Correct By: 06-Jun-2023 |
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm. The pool free chlorine residual was noted at 0ppm. Increase, then maintain the residual at 1.0ppm minimum. Ms. Michelson agreed to Voluntarily Close the pool. A POOL CLOSED sign was posted. Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 06-Jun-2023 |
Comments |
---|
All other violations were corrected. Thanks! Pool Notes: 1. The pool water is clear. 2. ACC unit pH noted at 7.5. 3. Turnover rate=10.6 hours. 4. Pool filter pressure gauge noted at 13psi. 4. All safety equipment is available. 5. ACC unit alarm functions when tested. Testing is documented in pool records. 6. The report was emailed to Swim Safe Pools. Contact Scott Bradley, R.E.H.S. (732-7614) with any questions. |