Inspection Information | Facility Name: | VILLAGE OF MCCOMB-SPLASH PAD |
---|---|
Facility Type: | Special Use |
[?] Inspection type: | Standard |
Inspection date: | 19-June-2018 |
3701-31-04 (B)(4)(a)(ii) Combined chlorine was not tested daily at pool side prior to use. Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use. |
3701-31-04 (B)(4)(a)(iv) Water temperatures were not being recorded daily. Take and record the water temperature at least once/day. |
Comments |
---|
Make sure to test and record flow switch monthly. Flow switch was tested at time of inspection and appeared to be operating correctly. |