Inspection Information | Facility Name: | RIVERSIDE PARK- DIVING |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 19-June-2017 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(i) Repeat A means of determining rate-of-flow was not found for all water pumps. Pump curve does not match the pump. Provide accurate pump curve. Properly install a flow meter or have a pump curve available for every water pump used for the pool. |
3701-31-04 (B)(6)(q) Repeat Depth markers/deck warning signs were not adequately spaced. Depth markers should be no farther apart than 25 feet. Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. |
3701-31-04 (E)(2)(b)(i) Corrected During Inspection USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool. Provide personal floatation device at the pool at all times. |
Comments |
---|
Observed a pump curve in the chemical room, however it does not appear to be the correct pump curve. |