Inspection Information | Facility Name: | CRYSTAL GLEN APARTMENTS |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 09-July-2018 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4)(a)(vi) Total alkalinity was not tested weekly. Test total alkalinity at least once/week. |
3701-31-04 (B)(6)(h) Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation. Flow meter appears to be broken and is reading above the measurable amount. Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. |
3701-31-04 (C)(2) pH was outside the range of 7.2 to 7.8. Treat the pool water so that the pH is within the acceptable range. |
3701-31-04 (C)(3) Total alkalinity was less than 60 ppm. Raise the total alkalinity to at least 60 ppm. |
Comments |
---|
Flow meter needs to be repaired or flow adjusted. Max amount of flow permitted for sand filter is 106 gpm. Minimum allowable flow is 71 gpm. |