Inspection Information | Facility Name: | CANTERBURY SWIM & TENNIS CLUB POOL |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 20-July-2022 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(f) Repeat Required turnover rates were not met. Increase the flow rate to at least 413 gpm. Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. |
3701-31-04 (B)(6)(o) Ladders/stairs/steps were not in good repair. The two ladders in the deep end are loose. Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair. |