Inspection Information | Facility Name: | CANTERBURY SWIM & TENNIS CLUB POOL |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 19-July-2021 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4)(a)(ii) Combined chlorine was not tested daily at pool side prior to use. Combined chlorine was not recorded on most days. Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use. |
3701-31-04 (B)(4)(a)(vi) Total alkalinity was not tested weekly. Test total alkalinity at least once/week. |
3701-31-04 (B)(4)(a)(vii) Cyanuric acid was not tested weekly. Test for cyanuric acid level at least once/week. |
3701-31-04 (B)(6)(f) Required turnover rates were not met. Required minimum flow is 413 gpm. At time of inspection, flow was at 300 gpm. Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. |
3701-31-04 (C)(2) pH was outside the range of 7.2 to 7.8. pH was at 7.0 at time of inspection. Treat the pool water so that the pH is within the acceptable range. |
Comments |
---|
Work on completing records. |