Inspection Information | Facility Name: | COMFORT INN OF BLUFFTON |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 01-December-2017 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(t) Corrected During Inspection Critical Repeat AT TIME OF INSPECTION THE DOORS TO THE POOL EQUIPMENT ROOM WAS OPEN. All equipment, chemical and other storeage areas shall be maintained in a clean condition, free from any hazards and ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL. (KEEP DOORS TO THE POOL EQUIPMENT AND CHEMICAL ROOM SHUT AND LOCKED) |
3701-31-04 (C)(2) pH was outside the range of 7.2 to 7.8. (AT TIME OF INSPECTION THE pH WAS 8.0) Treat the pool water so that the pH is within the acceptable range. (ADJUST CHEMISTRY SO THAT THE pH IS WITHIN ACCEPTABLE LIMITS) |
3701-31-04 (D)(7)(d) Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. (THIS NEEDS TO BE DONE AT A MINIMUM OF ONCE PER MONTH AND DOCUMENTED ON THE WEEKLY LOG) |
3701-31-04 (E)(3)(b) Repeat The unguarded pool was in use without the "Swimming alone is not recommended" signs posted. Post the "Swimming Alone is Not Recommended" signs at all times the pool is available for use. |