Inspection Information | Facility Name: | LAKEVIEW POOL & TENNIS CLUB |
---|---|
Facility Type: | Special Use |
[?] Inspection type: | Standard |
Inspection date: | 20-July-2020 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(c) Corrected During Inspection Critical Chlorine disinfectant residual was less than 2 ppm for the pool. Manager shocked the pool to raise chlorine residual to 5.0 ppm free chlorine. Make sure controller / feeder is able to maintain proper disinfectant residual at all times. Monitor regularly. Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. |
3701-31-04 (B)(6)(p) Concrete deck surface has some cracks, near the slide appears to be the most damaged. Contact Ohio Department of Health to submit plans prior to work being done. |
3701-31-04 (C)(3) Total alkalinity was less than 60 ppm. Raise the total alkalinity to at least 60 ppm. |
Comments |
---|
Manager removed patrons prior to hand feeding chlorine to bring pool into compliance. Make sure to monitor controller / feeder to ensure that chlorine residual is maintained. |