Inspection Information | Facility Name: | VILLAGE OF MCCOMB |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 29-July-2016 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(s) Entry gate is not self closing. Entry gate needs to be self closing, latching, and lockable. Repair spring of door hinge. |
3701-31-04 (D)(7)(d) Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly. Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. |
3701-31-04 (E)(2)(a)(ii) A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool. Flotation device is available, but there is not a rope attached to it. Attach a 1/4 inch rope to throw ring that is 30-60ft long. |
Comments |
---|
Repeat violations need to be addressed. Life guard certifications checked at time of inspection. Make sure to record alkalinity weekly. |