Inspection Information | Facility Name: | RIVERSIDE PARK- DIVING |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 27-May-2021 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (A) Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH). Submit ERN form for new pump/motor. Contact ODH to obtain approval for any construction/alterations before operating pool. |
3701-31-04 (B)(6)(i) A means of determining rate-of-flow was not found for all water pumps. Pump curve was not available at time of inspection. Properly install a flow meter or have a pump curve available for every water pump used for the pool. |
3701-31-04 (C)(2) pH was outside the range of 7.2 to 7.8. pH was at 7.0 Treat the pool water so that the pH is within the acceptable range. |
3701-31-04 (E)(2)(d) First aid equipment was not provided. Provide first aid equipment, including a first aid kit, at the pool at all times. |
Comments |
---|
Submit ERN for new circulation pump. Throw ring needs to have a rope of 30-60 feet if it is to be used. A follow up will be conducted on 5/28 to observe first aid kit, throw ring corrected. |