Inspection Information | Facility Name: | CANTERBURY SWIM CLUB |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 20-June-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4)(a)(iv) Water temperatures were not being recorded daily. Take and record the water temperature at least once/day. |
3701-31-04 (B)(4)(a)(vi) Total alkalinity was not tested weekly. Test total alkalinity at least once/week. |
3701-31-04 (B)(6)(f) Repeat Required turnover rates were not met. Pool flow rate was 390 gpm. Minimum required flow is 413 gpm. Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. |
3701-31-04 (B)(6)(o) Ladders/stairs/steps were not in good repair. Two ladders by the diving board are loose. Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair. |
Comments |
---|
Flow switch was tested at time of inspection. |