Inspection Information | Facility Name: | RIVERSIDE PARK- DIVING |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 09-August-2017 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(i) Repeat A means of determining rate-of-flow was not found for all water pumps. The pump curve in the chemical room does not appear to be correct. Motor for pool is 10 hp, however, the pump curve does not cover 10hp motors. Properly install a flow meter or have a pump curve available for every water pump used for the pool. |
Comments |
---|
Depth markers have been added. |