Inspection Information | Facility Name: | CANTERBURY SWIM CLUB |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 08-August-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4)(a)(iv) Water temperatures were not being recorded daily. Take and record the water temperature at least once/day. |
3701-31-04 (B)(6)(f) Repeat Required turnover rates were not met. Flow rate for the circulation system was at 359 gpm. Flow is required to be at 413 gpm or greater. Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. |
3701-31-04 (B)(6)(o) Repeat Ladders/stairs/steps were not in good repair. The pool ladder in the dive well was loose. Tighten ladders so that they are in good repair. |