Inspection Information | Facility Name: | COVINGTON GREEN APARTMENTS |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 12-June-2017 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6) Repeat The deck drain has a small area that is broken and a potential hazard. The broken area has a mat and safety cone in place to prevent injury. All equipment must be maintained in accordance with the manufacturers specifications. Work on repairing deck drains. |
3701-31-04 (B)(6)(f) Corrected During Inspection Required turnover rates were not met. Flow rate was at 50 gpm at time of inspection, filter was backwashed and flow is now at 100 gpm. Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. |
Comments |
---|
Manager is in the process of looking to repair drain covers. |