Inspection Information | Facility Name: | FINDLAY FAMILY YMCA - REHABILITATION SPA |
---|---|
Facility Type: | Spa |
[?] Inspection type: | Standard |
Inspection date: | 06-October-2020 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (A) Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH). Submit ERN for change in chlorine feeder. |
3701-31-04 (B)(6)(c) Cross connection hazards were present. The fill lines to each pump, 3 in total, were directly plumbed and create a cross connection hazard. Remove all direct connections to the water supply; Remove all cross connection hazards from the pool area. |
3701-31-04 (C)(7) Spa water temperature was greater than 104 degrees Fahrenheit. At time of inspection the temperature of the spa was at 105F. Operator adjusted heater at time of inspection. Do not operate the spa at a water temperature greater than 104 degrees Fahrenheit. Reduce the water temperature to 104 degrees or less. |
Comments |
---|
Submit ERN for new chlorine feeder. Direct connections to the water supply need to be removed. |