Inspection Information
Facility Name: EXTENDED STAY POOL
Facility Type: Pool
[?] Inspection type: Standard
Inspection date: 10-February-2015
Violations: A summary of the violations found during the inspection are listed below.
3701-31-04 (B)(6)(h)
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation. Replace missing flow meter for pool
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.
3701-31-04 (B)(6)(k)
Critical Outlet drain covers were not secure or were not in place. Replace missing equalizer covers on pool. Must be VGB compliant. Keep information on file of date and type installed.
Secure/install the outlet covers immediately to prevent entrapment/evisceration.
Comments
Install flow meter with 10x the diameter upstream and 5x the diameter downstream of unobstructed flow.


Inspection Outcome: