Inspection Information | Facility Name: | EXTENDED STAY POOL |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Follow-up |
Inspection date: | 25-September-2018 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4) Repeat The licensee /authorized representative was not keeping or maintaining operational records. The pool operator was not keeping records of when the flow switch was being tested. The records for chlorine was inconsistent. A reminder that the total chlorine is the free and combined added together. All facility records must be maintained and available for review upon request. |
3701-31-04 (C)(3) Repeat Total alkalinity was less than 60 ppm. At time of inspection, the alkalinity was 50 ppm. Raise the total alkalinity to at least 60 ppm. |
3701-31-04 (E)(2)(a)(i) Repeat 12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. The reach pole has a telescopic shepherd's crook. Provide a 12 ft. non-telescopic reach pole in the pool area at all times. |
3701-31-04 (E)(2)(e) Repeat Emergency device (telephone) was not working. The emergency phone has a busy signal when it is picked up. Ensure that the emergency device is functioning properly and rings to the emergency response authorities. |
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(6)(i)/A means of determining rate-of-flow on all water pumps A means of determining rate-of-flow was not found for all water pumps. At time of inspection, the flow meter was not showing a reading. Properly install a flow meter or have a pump curve available for every water pump used for the pool. |
Comments |
---|
A second follow-up inspection will be conducted on Tuesday, October 2 to observe corrected violations. |