Inspection Information | Facility Name: | RIVERSIDE PARK - SPLASH |
---|---|
Facility Type: | Special Use |
[?] Inspection type: | Standard |
Inspection date: | 21-June-2021 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(c) Critical Chlorine disinfectant residual was less than 2 ppm for the sprayground Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 2 ppm or above prior to placing the sprayground back into operation. |
3701-31-04 (B)(1)(e) Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. |
3701-31-04 (C)(3) Repeat Total alkalinity was less than 60 ppm. Alkalinity was at 30. Raise the total alkalinity to at least 60 ppm. |
Comments |
---|
Controller was not operating correctly and was not able to maintain adequate chlorine residual. Repairs have been ordered. Splash pad was closed during inspection. A follow up inspection will be conducted in 1-2 weeks to observe splash pad operating correctly. |