Inspection Information | Facility Name: | FINDLAY COUNTRY CLUB WADING POOL |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 21-June-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4)(a)(ii) Combined chlorine was not tested daily at pool side prior to use. Test for combined chlorine prior to bathers entering the water and every 12 hours while the pool is in use. |
3701-31-04 (B)(4)(a)(vi) Total alkalinity was not tested weekly. Test total alkalinity at least once/week. |
3701-31-04 (B)(6)(s) Gates or doors were not self-closing and lockable. The gate is not self closing and latching at time of inspection. Repair gates or doors in order to be self-closing, self latching and lockable. |