Inspection Information | Facility Name: | LAKEVIEW POOL & TENNIS CLUB |
---|---|
Facility Type: | Special Use |
[?] Inspection type: | Standard |
Inspection date: | 25-June-2019 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 ( D )(6)(a) ORP reading was below 650 mv. At time of inspection, the ORP reading was 358. Have the ACC unit inspected to determined why the ORP is low. |
3701-31-04 (B)(1)(c) Corrected During Inspection Critical Chlorine disinfectant residual was less than 1 ppm for the pool. The pool was shocked at time of inspection. After an hour, the chlorine was in compliance. Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. |
3701-31-04 (C)(2) pH was outside the range of 7.2 to 7.8. At time of inspection, the pH was 8. Treat the pool water so that the pH is within the acceptable range. |
Comments |
---|
Lifeguard certifications, emergency phone, and safety equipment was checked at time of inspection. Be sure to keep chemicals balanced and in compliance. |