3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Observed ORP displaying on ACC as 600 millivolts. When discussing with operator, he stated that when he has the ORP raised to the required minimum of 650, the chlorine levels in the pool goes above 10 ppm. He also noted, that when the cyanuric acid decreases, the ORP increases.
Recommend having ACC serviced in case it is the issue.
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Repeat Observed cyanuric acid (which pool operator uses) not being recorded as tested weekly on pool log.
Check and record cyanuric acid level weekly on pool log.
3701-31-04 (B)(5) / Records are maintained for at least two years
Repeat Main drain paperwork was not readily available on-site. Operator noted, if feasible, main drains are going to be replaced before next operating season.
If new covers are installed, ensure the install date is added to the paperwork and kept on file at the pool area.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rate was not met as minimum flow rate was not reached per flow meter. Flow meter reading was 100gpm and minimum flow rate to achieve the required turnover rate is 250gpm.
Have the circulation system evaluated to determine why the turnover rates are not bale to be met. Once the reason(s) have been determined, have issue repaired. If neccessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Observed loose ladders at left side of pool at 3ft mark and at 12 ft mark. Observed faded slip grip coating at white floating stairs in shallow end.
Tighten down loose ladders and re-apply slip grip coating to white stairs.
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
Repeat Observed 12 ft. telescopic reach pool at 12 ft depth level of pool.
Purchase a 12 ft. non-telescopic reach pole for pool.
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Repeat Observed no signage at pool stating where to find emergency phone/that emergency phone is located at concession stand register.
Add signage at pool area that states where emergency phone is located.
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 10-August-2022