3701-31-04 (B)(4)(a)(v) / Water clarity are not present
Water clarity was not being recorded in the water quality logs.
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly and not recorded in the water quality logs.
Test for cyanuric acid level at least once/week.
3701-31-04 (B)(6)(n) / Proper pool operating water level is maintained
At time of inspection, observed slightly low water level. It was also observed that the weirs of the two skimmers closest to the steps were not open and/or stuck, not allowing the water to be drained.
Increase the volume of the pool water until the pool operating water level is restored.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat At time of inspection, observed a pH of 7.0, which is below the acceptable range.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. The shepherd's crook that is provided is only 8.5 ft. long.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
Facility Type: Spa
Inspection Type: Consultation
Inspection Date: 03-August-2023