3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. The flow meter is reading 62gpm. The minimum required flow for this pool is 81gp. Backwashing the filter may help increase the flow. Correct By: 10-Jun-2015
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times. Correct By: 10-Jun-2015
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 26-May-2015