3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
Repeat Observed no not water available at hand wash sink in women's restroom. Observed burned out light above toilet stall in the men's restroom.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met due to improper flow rates. A flow rate of 180 GPM was observed, the minimum is 250 GPM.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Observed a few loose ladders and worn slip resistance on ladders at the pool deck.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 09-August-2023