3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
Observed some deteriorated concrete at pool deck. Observed peeling paint on pool floor. Observed scum line along perimeter of pool at water surface; recommend cleaning this area daily.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine shall be measured and recorded in the water quality logs each time the chlorine residual is tested.
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Corrected During Inspection At time of inspection, observed equipment/pump room left unlocked during operation hours. Discussed issue with PIC on site and door was locked immediately.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Observed alkalinity (50 ppm) below the required mininum; recommend dosing some soda ash and/or adding fresh fill water as needed.
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 03-August-2022
Comments |
---|
At time of inspection, water level appeared to be low. |