3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. Correct By: 25-Jun-2014
3701-31-04 (D)(5) / Cyanuric acid level does not exceed 70 ppm
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly. Correct By: 25-Jun-2014
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 11-June-2014