3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
Broken tiles/crack in tiling near office 023.
Broken tiles/cracks in tiling need to be repaired.
3701-31-04 (B)(4)(a)(v) / Water clarity are not present
Water clarity was not recorded on pool logs.
Ensure water clarity is recorded daily.
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was observed at 7.0 ppm.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was observed at 50 ppm
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
Facility Type: Pool
Inspection Type: Consultation
Inspection Date: 03-August-2023
Comments |
---|
Inspection was conducted per an ODH annual pool program survey. |