[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. Observed the flow at 175 gpm, the required minimum flow for this facility is 250 gpm.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


Facility Type: Pool

Inspection Type: Standard

Inspection Date: 21-June-2018

Comments
The main pool and wading pool are on the same circulation system.