3701-31-04 (B)(6)(n) / Proper pool operating water level is maintained
Water observed below halfway point at pool skimmers.
Fill pool to a depth where water hits halfway mark at skimmers.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Observed pH testing at 7.0. It is noted that ACC indicates pH is at 7.4. Recommend calibrating ACC.
Calibrate ACC and retest pool pH.
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Telephone has no signal. A work order is in to fix this issue.
As pool is open at same time as concession stand, concession stand attendent is to utilize cell phone and have a charger to charge cell phone on premise until pool telephone is repaired.
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 11-July-2022
Comments |
---|
New/ additional signage stating verbatim "Warning, No Lifeguard," "Swimming Alone Is Not Recommended," and Children Must Be Supervised" needed for pool. |