3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical At time of inspection observed disinfection residual to be at .5 ppm of chlorine, the minimum required is 1 ppm of chlorine.
Recommend that the wading pool be roped off and closed until the minimum required disinfection residuals are met. Per the pool operator, the wading pool was closed once found that the minimum disinfection residual was not met. Correct By: 12-Jul-2018
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 10-July-2018
Comments |
---|
This is a follow up, at last inspection the wading pool was already closed due to not having the minimum required disinfection residual. Noted, upon inspection, the minimum chlorine residual was not met and per the pool operator the wading pool was roped off and closed until the minimum chlorine residual is met. |