3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was tested at 30 ppm at time of inspection.
Raise the total alkalinity to at least 60 ppm.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Pool free chlorine disinfectant residual was observed only slightly above 0 ppm at time of inspection.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 12-Jul-2018
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 11-July-2018
Comments |
---|
Wading pool will be closed until it reaches the proper chemical concentration. |