3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(5) / Records are maintained for at least two years
No paperwork available for main drains. However, main drains were replaced this season.
Maintain all records and have them available upon request.
3701-31-04 (B)(6)(c)(iii) / Floor areas in equipment, filter and storage rooms shall be free of standing water
Observed multiple leaks on plumbing equipment in pump room.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Flow meter observed inoperable as bobber was stuck in meter.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Multiple loose ladders observed on pool deck.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 15-June-2021
Comments |
---|
Observed sand/debris on deep end of pool near main drains. Observed the visual alarm initiated on the ACC for main pool. Discussed with management and they noted this issue will be resolved. |