3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
Facility Type: Pool
Inspection Type: Follow-up
Inspection Date: 24-July-2019
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required. Chlorine disinfectant residual was less than 1 ppm for the pool Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. |
3701-31-04 (B)(4)(a)(iv)/Water temperatures are recorded daily Water temperatures were not being recorded daily. Take and record the water temperature at least once/day. |
3701-31-04 (B)(6)(f)/Required turnover rates are sufficient Required turnover rates were not met. Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. |
Comments |
---|
***CHLORINE LEVELS ARE NOW COMPLIANT*** |