3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. Observed the flow meter at 175 gpm, the required minimum flow is 250 gpm for this facility.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (B)(6)(r) / Safety line(s) are maintained
Safety line(s) were not maintained in place. The safety line was not present during time of inspection because the hook that connects the line was broken.
Safety lines must be in place when required to alert the bathers of the change in depth of the pool.
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool. Observed no ring buoy with throw line present at time of inspection.
Provide a proper floatation device at all times.
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 21-June-2018
Comments |
---|
The hose bib in the pump room is leaking water onto the pump room floor, spoke with operator about tightening hose bib as to prevent the leak. Spoke to operator about providing dates on the records sheets. |