3701-31-04 (B)(5) / Records are maintained for at least two years
Main drain paperwork was not available for review, but action plan was discussed on-site today with pool maintenance staff.
Maintain all records and have them available upon request.
3701-31-04 (B)(6)(c)(iii) / Floor areas in equipment, filter and storage rooms shall be free of standing water
Water on the floor underneath the pump.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Turnover rate was not met as flow rate was observed at 40 gpm and the minimum flow rate is 49 gpm.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 20-July-2021