3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
Seat cover in women's shower area was observed torn and cracking.
3701-31-04 (B)(5) / Records are maintained for at least two years
Repeat Main drain paperwork not available on-site.
Maintain all records and have them available upon request.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rate was not met as minimum flow rate was not reach per flow meter. Flow reading from flow meter was 100 gpm and the minimum flow rate to achieve the required turnover rate is 250 gpm.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders near pool entry area were loose and were removable upon observation.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Entry gate to pool was observed propped open.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm, as it was tested at 50 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. Observed a telescopic reach pool in the pool area.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
3701-31-04 (E)(2)(b)(ii) / A back/spine board with straps and head immobilizers
Repeat A back/spine board with straps and head immobilizers was not provided at the guarded pool.
Provide a back/spine board with straps and a head immobilizer at the pool at all times.
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 28-July-2021