3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. At pool-side, the pH was 8.0.
Treat the pool water so that the pH is within the acceptable range. Correct By: 16-Aug-2016
Facility Type: Pool
Inspection Type: Follow-up
Inspection Date: 02-August-2016
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required. The minimum disinfection residual of 1 ppm was not maintained as required. At pool-side, the disinfection residual was measured at 0.5 ppm. Maintain a disinfection residual of 1 ppm or greater as required. Do not open the pool to swimmers until the minimum disinfection residual is restored. Correct By: 02-Aug-2016 |
Comments |
---|
At the time of inspection, the top of the strainer appeared to be leaking. Please have the strainer evaluated and fixed as needed. |