3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Observed replacement of pump was completed but not like-for-like make and model. Operator shall submit ERN form to ODH for approval.
3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
Repeat Observed concrete pulling away from the pool edge on shallow side of the pool. Observed concrete cracking and deterioration surrounding the ladder by the lifeguard stand at the 12ft side of the pool. Observed peeling of surfacing material on the diving board. Observed deterioration of concrete wall behind the diving boards.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Flow rate not sufficient due to being observed at 450 gpm; minimum rate needed to reach 479 gpm.
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook was not provided at the guarded pool.
3701-31-04 (E)(4)(b) / Written plan for lifeguard coverage available for all pools 6,000 sq. ft or larger
After discussion with operator, written plan for adequate lifeguard coverage will need to include a diagram indicating location of lifeguard station and coverage.
Facility Type: Pool
Inspection Type: Standard
Inspection Date: 06-June-2023